Страница 1
Baxi Solo 3 PF Wall Mounted Powered Flue Gas Fired Central Heating Unit Installation and Servicing Instructions Please leave these instructions with the user
Страница 1 PDF
Страница 2
2 Baxi UK Limited is one of the leading manufacturers of domestic heating products in the UK. Our first priority is to give a high quality service to our customers. Quality is built into every Baxi product - products which fulfil the demands and needs of customers, offering choice, efficiency and reliability. To keep ahead of changing trends, we have made a commitment to develop new ideas using the latest technology - with the aim of continuing to make the products that customers want to buy. Everyone who works at Baxi has a commitment to quality because we know that satisfied customers mean continued success. We hope you get a satisfactory service from Baxi. If not, please let us know. Natural Gas Baxi Solo 3 30 PF G.C.No. 41 075 04 Baxi Solo 3 40 PF G.C.No. 41 075 05 Baxi Solo 3 50 PF G.C.No. 41 075 06 Baxi Solo 3 60 PF G.C.No. 41 075 07 Baxi Solo 3 70 PF G.C.No. 41 075 08 Baxi Solo 3 80 PF G.C.No. 41 075 09 Baxi is a BS-EN ISO 9001 Accredited Company The boiler meets requirements of Statutory Instrument “The Boiler (Efficiency) Regulations 1993 No 3083” and is deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:- Type test for purpose of Regulation 5 certified by: Notified Body 0086. Product/Production certified by: Notified Body 0086. For GB / IE only.
Страница 2 PDF
Страница 3
3 1.0 Introduction 4 2.0 Technical Data 5 3.0 System Details 7 4.0 Site Requirement 10 5.0 Installation 14 6.0 Commissioning the Appliance 32 7.0 Fitting the Outercase 34 8.0 Overheat Cut-Off Device 35 9.0 Annual Servicing 36 10.0 Changing Components 38 11.0 Fault Finding 42 12.0 Short Parts List 44 13.0 Notes 45 Section Page Contents
Страница 3 PDF
Страница 4
1.0 Introduction 4 1 STANDARD B.S. 6891 B.S. 5546 B.S. 5449 B.S. 6798 B.S. 5440: Pt 1 B.S. 5440: Pt 2 B.S. 7593 B.S. 4814 B.S. 6283 SCOPE Gas Installation. Installation of hot water supplies for domestic purposes. Forced circulation hot water systems. Installation of gas fired hot water boilers. Flues. Ventilation. Water Treatment. Expansion vessels for hot water systems. Safety and control devices for use in hot water systems. HEAT OUTPUT Q Model Min Max 30 5.86kW (20,000 Btu/h) 8.79kW (30,000 Btu/h) 40 9.09kW (31,000 Btu/h) 11.72kW (40,000 Btu/h) 50 12.02kW (41,000 Btu/h) 14.65kW (50,000 Btu/h) 60 14.95kW (51,000 Btu/h) 17.58kW (60,000 Btu/h) 70 17.88kW (61,000 Btu/h) 20.5kW (70,000 Btu/h) 80 20.8kW (71,000 Btu/h) 23.45kW (80,000 Btu/h) B.S. Codes of Practice, most recent version should be used 1.1 Description 1. The Baxi Solo 3 PF is a gas fired room sealed fan assisted central heating boiler with range rated outputs as shown in the table below 2. Each appliance is preset at a MID RANGE heat input rating and is designed for use on NATURAL GAS only. 3. All boilers are suitable for fully pumped open vented central heating and domestic hot water systems and sealed systems. 4. The appliance data badge is fitted to the combustion box door. 1.2 Installation 1. The appliance is suitable for installation only in G.B. and I.E. and should be installed in accordance with the rules in force. For Ireland install in accordance with I.S.813 “INSTALLATION OF GAS APPLIANCES”. The installation must be carried out by a CORGI Registered Installer or other competent person and be in accordance with the relevant requirements of the current GAS SAFETY (Installation and Use) REGULATIONS, the BUILDING REGULATIONS (Scotland) (Consolidation), the LOCAL BUILDING REGULATIONS, the CURRENT I.E.E. WIRING REGULATIONS and the bye laws of the Local Water Undertaking. Where no specific instructions are given, reference should be made to the relevant current BRITISH STANDARD CODES OF PRACTICE. 2. All systems must be thoroughly flushed and treated with inhibitor (see Section 3.1). 1.3 Important Information Man-Made Mineral Fibre a) Some component parts of this appliance (insulation pads, gaskets and rope seals) are manufactured from man-made mineral fibre. b) Prolonged or excessive exposure to this material may result in some irritation to the eyes, skin or respiratory tract. c) It is advisable to wear gloves when handling these items. d) Irritant dust will only be released from the items if they are broken up or subjected to severe abrasion. In these instances a suitable dust mask and goggles should be worn. e) Always thoroughly wash hands after installation, servicing or changing components. f) When disposing of any items manufactured from man-made mineral fibre care must be exercised. g) If any irritation of the eyes or severe irritation of the skin is experienced seek medical attention. IMPORTANT: State of adjustment - Check that the state of adjustment given on the data plate is compatible with local supply conditions. “Benchmark” Log Book As part of the industry-wide “Benchmark” intiative all Baxi boilers now include an Installation, Commissioning and Service Record Log Book. Please read the Log Book carefully and complete all sections relevant to the appliance and installation. These include sections on the type of controls employed, flushing the system, burner operating pressure etc. The details of the Log Book will be required in the event of any warranty work. Also, there is a section to be completed at each subsequent regular service visit.
Страница 4 PDF
Страница 5
2.0 Technical Data 1 5 Model 30 40 50 60 70 80 P Heat Output (Max) kW 8.79 11.72 14.65 17.58 20.5 23.45 Btu/h 30,000 40,000 50,000 60,000 70,000 80,000 P Heat Output (Min) kW 5.86 9.09 12.02 14.95 17.88 20.8 Btu/h 20,000 31,000 41,000 51,000 61,000 71,000 Q Heat Input (Max) kW 10.99 14.65 18.32 21.98 25.64 29.31 Btu/h 37,500 50,000 62,500 75,000 87,500 100,000 Q Heat Input (Min) kW 7.33 11.36 15.02 18.68 22.35 26.01 Btu/h 25,000 38,750 51,250 63,750 76,250 88,750 Burner Pressure (Max) mbar 16.0 ±0.5 16.0 ±0.5 16.0 ±0.5 16.0 ±0.5 16.0 ±0.5 16.0 ±0.5 in wg 6.4 ±0.2 6.4 ±0.2 6.4 ±0.2 6.4 ±0.2 6.4 ±0.2 6.4 ±0.2 Burner Pressure (Min) mbar 8.0 ±0.5 10.0 ±0.5 11.5 ±0.5 11.5 ±0.5 12.1 ±0.5 11.5 ±0.5 in wg 3.2 ±0.2 4.0 ±0.2 4.4 ±0.2 4.4 ±0.2 4.8 ±0.2 4.4 ±0.2 Gas Rate CV 38mj/m3 1.04m3/h 1.39m3/h 1.74m3/h 2.08m3/h 2.43m3/h 2.78m3/h (after 10 mins) 36.86ft3/h 49.0ft3/h 61.3ft3/h 73.5ft3/h 86.75ft3/h 98.1ft3/h Lifting Weight kg 23.1 23.1 23.1 32.2 32.2 32.2 lbs 51 51 51 71 71 71 Water Content litres 1.1 1.1 1.1 1.6 1.6 1.6 pints 1.9 1.9 1.9 2.8 2.8 2.8 Outercase Height 600mm 600mm 600mm 600mm 600mm 600mm Dimensions Width 350mm 350mm 350mm 462mm 462mm 462mm Depth 287mm 287mm 287mm 287mm 287mm 287mm Flue Terminal Diameter 100mm Dimensions Depth 70mm Static Head Max 30 metres (100 ft) Min 1 metre (3.25 ft) Connections Flow 22mm Cu tail Return 22mm Cu elbow Heat Exchanger Cast iron monobloc Low Head Min 0.2m (8 in) System Design fully pumped open vented and sealed systems Gas Connection RC1/2 (1/2 in BSPT) Electrical Supply 230V ~ 50Hz fused 5A - 90W Controls boiler thermostat, intermittent pilot & electronic flame sensing, timed pump over-run, frost protection thermostat Internal Fuse 4AF 250V to BS4256 situated on control board
Страница 5 PDF
Страница 6
2.0 Technical Data 6 25 75 121 392 439 442 268 144 144 4 107 Dia without internal fitting 117 Dia with internal fitting Centre of Gas Connection 8 Slots 20 x 6 Layout of Fixing Points 30, 40 and 50 PF models 25 75 121 392 439 442 380 196 196 52 107 Dia without internal fitting 117 Dia with internal fitting Centre of Gas Connection 8 Slots 20 x 6 Layout of Fixing Points 60, 70 and 80 PF models (4) 10 (8) 20 (16) 40 (24) 60 (12) 30 (20) 50 (28) 70 (32) 80 (36) 90 (40) 100 (44) 110 (48) 120 2 4 6 8 10121416182022 Water Flow Rate litres / min Pressure Drop mbar (in wg) 242628 30 (52) 130 (4) 10 (8) 20 (16) 40 (24) 60 (12) 30 (20) 50 (28) 70 (32) 80 (36) 90 (40) 100 (44) 110 (48) 120 2 4 6 8 10121416182022 Water Flow Rate litres / min Pressure Drop mbar (in wg) 242628 30 (52) 130 30, 40 and 50 PF models 60, 70 and 80 PF models Templates Hydraulic Resistance Charts • This appliance is only intended for installation on a governed supply. • PMS = 3 bar pressure class 2 • Max CH water pressure 3 bar • Type C12, C32, C52 • Nox class 2 • Appliance category I2H 2H - G20 - 20mbar • Ref: 86/AU/588 • Burner Injector Sizes: 30=B12 40=B13 50=B14 60=B15 70=B30 80=B16 • This boiler is designed to operate at a maximum water temperature of 85° C. 61.3mm Model Seasonal Efficiency (SEDBUK) (%) 30 78.8 40 77.8 50 76.7 60 77.8 70 77.7 80 77.8 This value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated have been certified by 0086. SEDBUK Declaration For Solo 3 PF All Models 121mm Top of Outercase
Страница 6 PDF
Страница 7
3.0 System Details 7 Typical Systems Arrangement Option A Boiler Pump Air Vent Radiator Circuit Fully Pumped System Air Vent Radiator Circuit Twin Zone Valve System Air Vent Radiator Circuit 3 Port Divertor Valve System Option B Radiator Circuit Option C Fig. 1 Fig. 2 Fig. 3 Fig. 4 Examples of systems which require a bypass are:- a) A system controlled by non-electrical valves e.g. mechanical thermostatic control valves both on the radiators and the hot water circuit. b) A system using twin zone valves (e.g. Honeywell 'S' Plan) (Fig. 3). c) A system using a 3 port divertor valve (Fig. 4) does not normally require a bypass therefore this system is recommended. The exception to this is where thermostatic radiator valves are used and then a bypass is required. NOTE: For ‘S’ Plan systems the bypass flow circuit must be situated between pump and zone valves as option A shows (Fig. 2). The bypass circuit can be:- a) For all boilers a minimum of 6 metres of 22mm copper pipe, (measured between the boiler flow and return connections). It should be fitted with a lock shield valve opened at least 1 full turn or a proprietary bypass valve set to give a minimum flow rate of 8 litres/min (1.8 gal/min) (Option C, Fig. 1 & Option A, Fig.2). b) A radiator fitted with lock shield valves. The radiator output should be a minimum of 800 watts (2,700 Btu/h). Typically a convector type radiator with an area of 3750 cm2 (4 sq ft) is adequate (Option B, Fig. 1). c) Any circuit that provides the same operating conditions as option A or option B (Figs. 1 & 2). 3.1 Water Circulating Systems 1. The appliance is suitable for use with open vent fully pumped systems and sealed systems where additional control protection is required. The following conditions should be observed on all systems: • The static head must not exceed 30m (100ft) of water. • The boiler must not be used with a direct cylinder. • The boiler is fitted with a timed pump overrun that will operate for approximately 8 minutes. • Drain cocks should be fitted to all system low points. • All gas and water pipes and electrical wiring must be installed in a way which would not restrict the servicing of the boiler. • Position isolating valves as close to circulating pump as possible. Treatment of Water Circulating Systems • All recirculatory water systems will be subject to corrosion unless an appropriate water treatment is applied. This means that the efficiency of the system will deteriorate as corrosion sludge accumulates within the system, risking damage to pump and valves, boiler noise and circulation problems. • For optimum performance after installation this boiler and its associated central heating system must be flushed in accordance with the guidelines given in BS 7593:1992 “Treatment of water in domestic hot water central heating systems”. • This must involve the use of a proprietary cleanser, such as BetzDearborn Sentinel X300 or X400, or Fernox Superfloc. Full instructions are supplied with the products, but for immediate information please contact BetzDearborn (0151 420 9563) or Fernox (01799 550 811) directly. • For long term protection against corrosion and scale, after flushing it is recommended that an inhibitor such as BetzDearborn Sentinel X100, or Fernox MB-1 or Copal is dosed in accordance with the guidelines given in BS 7593:1992. Failure to flush and add inhibitor to the system may invalidate the appliance warranty. • It is important to check the inhibitor concentration after installation, system modification and at every service in accordance with the inhibitor manufacturer’s instructions. (Test kits are available from inhibitor stockists.) • For information or advice regarding any of the above contact the Baxi Helpline. 3.2 Bypass Requirements 1. The boiler is fitted with a pump overrun device which allows the removal of residual heat from the boiler. NOTE: The pump overrun will operate for approximately 8 minutes. The system design must therefore, always provide an open circuit for water to circulate between the boiler flow and return. 2. See information opposite “Examples of systems which require a bypass are”.
Страница 7 PDF
Страница 8
3.0 System Details 8 3.3 Pipework 1. The sizes of flow and return pipes from the boiler should be determined by normal methods, according to the requirements of the system. 2. An 11 °C (20°F) drop in temperature across the system is recommended. 3. In systems using non-metallic pipework it is necessary to use copper pipe for the boiler Flow and Return. The copper must extend at least 1 metre from the boiler and include any branches (Fig. 4a). The copper pipe must not be insulated. 3.4 System Controls 1. For optimum operating conditions, the heating system into which the boiler is installed should include a control system. 2. Such a system will comprise of a timer control and separate room or cylinder thermostats as appropriate. 3. The boiler should be controlled so that it operates on demand only. 4. Operation of the system under control of the boiler thermostat only does not produce the best results. 5. A frost thermostat is fitted integrally to the appliance controls and will protect the boiler from frost damage by operating the burner when the water temperature in the boiler drops towards freezing point. The boiler will fire as necessary to maintain a temperature above freezing. NOTE: The frost thermostat operates even if the boiler thermostat is in the OFF ('0') position and it is necessary therefore, if the system is drained, for the external electrical and gas supplies to be isolated. It is recommended that a label be affixed to the appliance to draw attention to the fact that the system has been drained. 3.5 Low Head Installation For boilers up to 50,000 Btu/h output 1. Using a close coupled arrangement the minimum head is as shown in the diagrams (Figs. 5 & 6) subject to the following conditions: a) The correct heat input. b) The pump being adjusted to give an 11oC drop across the boiler. c) The pump must be fitted on the flow. d) The pump must be fitted in accordance with the pump manufacturer's instructions. e) The open vent pipe must be taken up from a tee in a horizontal section of the flow pipe. Alternative Low Head Installation for all Solo 3 PF (Fig. 7) 2. If less height is available then a combined vent and feed pipe may be connected. This must be a minimum of 22mm diameter. It is recommended that an air separator is fitted when using a combined feed and vent pipe. Typical Low Head Installation If Conditions Require, This System Possible Alternative Low Head Installation Boiler 500mm 45° 22mm Open Vent 1000mm Min 150mm Max 15mm Cold Feed 400mm Min Head Return Pump Flow Boiler 500mm 45° 22mm Open Vent 400mm Min Head 1000mm Min Automatic Air Vent 15mm Cold Feed 150mm Max Return Pump Flow Return Pump Flow Boiler 200mm Min Air Separator 22mm Feed & Vent Pipe Fig. 5 Fig. 6 Fig. 7 Boiler Flow Return Copper 0.5m Copper 1m Copper 0.5m Fig. 4a
Страница 8 PDF
Страница 9
3.0 System Details 9 3.6 Sealed Systems (Fig. 8) 1. SAFETY VALVE - A safety valve complying with the requirements of BS 6283 Part 1 must be fitted close to the boiler on the flow pipe by means of a horizontal or vertically upward connection with no intervening valve or restrictions and should be positioned to facilitate testing. The valve should be pre-set and non-adjustable to operate at a pressure of 3 bar (45 Ibf/in2). It must be arranged to discharge any water or steam through a pipe to a safe outlet position. 2. PRESSURE GAUGE - A pressure gauge of minimum range 0-4 bar (0-60 Ibf/in2) with a fill pressure indicator must be fitted to the system, preferably at the same point as the expansion vessel in an easily visible position. 3. EXPANSION VESSEL - An expansion vessel complying with the requirements of BS 4814 must be fitted to the system by means of a connection close to the inlet side of the circulating pump in accordance with the manufacturers instructions, the connecting pipe being unrestricted and not less than 15mm (1/2 in) nominal size. The volume of the vessel should be suitable for the system water content and the nitrogen or air charge pressure should not be less than the system static head (See Table. 1). Further details of sealed system design can be obtained from BS 5449 and the British Gas publication entitled 'Specifications for Domestic Wet Central Heating Systems'. 4. FILLING POINT - A filling point and an approved stop valve to BS 1010 must be fitted at low level and the method used for filling the system should be approved by the local water undertaking. For further details see BS 6798. 5. MAKE UP SYSTEM - A method of replacing water lost from the system should be provided either by means of a make up vessel of not more than 3 litres (5 pints) capacity, mounted above the highest point of the system, or by pre- pressurisation of the system. 6. VENTING - A method of venting the system during filling and commissioning must be provided by fitting automatic air vents or by venting manually. 7. HOT WATER STORAGE - The hot water storage vessel must be of the indirect coil type. 8. SYSTEM COMPONENTS - All components used in the system must be suitable for operation at 110°C (230°F) and at the pressure allowed by the safety valve. Initial System Pressure (Bar) Vessel Charge Pressure (Bar) Multiply Total Water Content Of System By (Litres) 0.067 0.112 0.207 0.441 0.087 0.152 0.330 0.125 0.265 0.5 1.0 1.5 2.0 1.0 1.5 2.0 1.5 2.0 0.5 1.0 1.5 Example :- Then :- System Volume = 75 litres Vessel Charge Pressure = 1.0 bar Initial System Pressure = 1.5 bar 75 x 0.152 = 11.4 litres Expansion Vessel Volume Method of determining minimum value of expansion vessel volume for sealed systems using Baxi Boilers NOTE Where a vessel of the calculated size is not obtainable then the next available larger size should be used. Safety Valve Pressure Gauge Pump Filling Point Air Vent 3 Litre Top Up Bottle (if required) Radiator Circuit Expansion Vessel System Drains at Low Point Max Boiler Flow Temp = 82° C Boiler Fig. 8 Table. 1
Страница 9 PDF
Страница 10
4.0 Site Requirements 10 4.1 Location 1. The appliance may be fitted to any suitable wall with the flue passing through an outside wall and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The appliance should be fitted within the building unless otherwise protected by a suitable enclosure ie. garage or outhouse. (The appliance may be fitted inside a cupboard. Cooling ventilation and insulation of the cupboard are not required, see section 4.5.) 2. If the appliance is fitted in a room containing a bath or shower reference must be made to the Current I.E.E. Wiring Regulations and Building Regulations. If the appliance is to be fitted into a building of timber frame construction then reference must be made to the Institute of Gas Engineers document UP7 - Guide for Gas Installations in Timber Framed Dwellings. 3. Recommendations for flues are given in BS 5440 Part 1. 4.2 Minimum Clearances (Fig. 9) 1. A flat vertical area is required for the installation of the boiler measuring as shown in the table below for each model. 2. These dimensions include the necessary clearances around the appliance for case removal, spanner access and air movement. Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the front face of the appliance. 3. If fitted inside a cupboard the clearance of 300mm shown is only necessary when the cupboard door is open. A clearance of 5mm (3/16 in) is required when the door is closed. 4.3 Flue Position 1. For installations where the flue terminal is inaccessible from the outside, an internal fitting kit is available. This can be obtained free of charge from your local merchant. 2. The following guide lines indicate the general requirements for siting balanced flue terminals. 3. If the terminal is fitted within 1 metre (39in) of a plastic gutter, within 500mm (191/2 in) of a painted eave or a painted gutter, an aluminium shield of at least 1 metre (39in) long should be fitted to the underside of the gutter or painted surface. An air space of 5mm (3/16 in) should be left between shield and gutter (Fig. 10). 4. If the terminal discharges onto a pathway or passageway, check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway. 5. If the outer surface of an outside wall is of combustible material, it should be protected by fitting the flue trim provided. Fig. 9 Fig. 10 300mm for servicing 5mm during operation 5mm 5mm 350mm (30,40,50 models) 600mm 50mm 100mm 462mm (60,70,80 models) Aluminium Shield Model Height Width mm (in) mm (in) 30 750 (291/2) 360 (141/8) 40 750 (291/2) 360 (141/8) 50 750 (291/2) 360 (141/8) 60 750 (291/2) 472 (185/8) 70 750 (291/2) 472 (185/8) 80 750 (291/2) 472 (185/8) 287mm
Страница 10 PDF
Страница 11
4.0 Site Requirements 11 4.3 Flue Position (Cont) WARNING - The addition of anything that may interfere with the normal operation of the appliance (e.g. FLUE DAMPERS, ECONOMISERS,etc.) without the express written permission of Baxi UK Limited could invalidate the appliance warranty and infringe the GAS SAFETY (Installation and Use) REGULATIONS. If a terminal is less than 2 metres (783/4 in) above a balcony, above ground or above a flat roof to which people have access then a suitable terminal guard must be provided. 6. Table 2 and Fig. 11 show the positioning of the flue terminal relative to buildings and other structures. 7. The dimensions of the flue terminal are shown on page 5. 4.4 Flue Dimensions 1. Flue extensions are available as optional extras for installations up to 3 metres (1181/8 in). 2. Vertical flue kits are available up to 4 metres in length. Vertical twin flue kits are available up to 15 metres in length. IMPORTANT: Solo 3 30 PF models must not be set at minimum input when installed with vertical flue systems. 3. The standard telscopic flue is suitable for use with rear flue lengths between 100mm (4in) and 500mm (195/8 in). NOTE: Maximum flue length when flued to the left or right is 410mm (16in) - 30, 40, 50 PF 355mm (14in) - 60, 70, 80 PF 4. Where it is intended to pass the flue through a combustible wall or timber framed dwelling, reference should be made to the Institute of Gas Engineers document UP7 - Guide for Gas Installations in Timber Framed Dwellings. 5. If the flue is more than 1 metre (39 in) long, it is required that it is supported. 6. All above dimensions are taken from the respective faces of the outer case. Table. 2 Fig. 12 Fig. 11 Terminal Position with Minimum Distance (mm) A Directly below an openable window or other opening, e.g. an air brick. 300 B Below gutters. 25 C Below eaves, soil pipes or drain pipes. 75 D Below balconies or car port roof 200 E From vertical drain pipes and soil pipes. 75 F From internal or external corners. 25 G Above ground, roof or balcony level. 300 H From a surface facing a terminal. 600 I From a terminal facing a terminal. 1200 J Vertically from a terminal on the same wall. 1500 K Horizontally from a terminal on the same wall. 300 L For an opening in a car port (e.g. door, window) into a dwelling. 1200 K G G E L D J G A A D F H,I B,C F Likely flue positions requiring a flue terminal guard Maximum lengths for side flues using the standard telescopic flue kit 410mm (30, 40, 50) 410mm (30, 40, 50) 355mm (60, 70, 80) 355mm (60, 70, 80)
Страница 11 PDF
Страница 12
4.0 Site Requirements 12 4.5 Ventilation of Compartments 1. Where the appliance is installed in a cupboard or compartment, no air vents are required. NOTE: The ventilation label on the front of the outer case MUST NOT BE REMOVED when the appliance is installed in a compartment or cupboard. 2. B.S. 5440 refers to room sealed appliances installed in compartments. The Solo 3 PF will run sufficiently cool without ventilation. 4.6 Gas Supply (Fig. 13) 1. The gas installation should be in accordance with BS 6891. 2. The connection of the appliance is a RC1/2 (1/2 in BSPT internal) located at the rear of the gas cock. 3. Ensure that the pipework from the meter to the appliance is of adequate size. Do not use pipes of a smaller diameter than the appliance gas connection. 4.7 Electrical Supply External wiring must be correctly earthed, polarized and in accordance with CURRENT I.E.E. WIRING REGULATIONS. The mains supply is 230V ~ 50Hz fused at 5A. NOTE: The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance. Connection may be made via a fused double- pole isolator with a contact separation of a least 3mm in all poles and serving the appliance and system controls only. Fig. 13
Страница 12 PDF
Страница 13
4.0 Site Requirement 13 4.8 Flue Options 1. The Baxi Solo 3 PF can be fitted with flue systems as illustrated. 2, The standard flue is suitable only for horizontal applications. 3. Maximum permissible equivalent flue lengths are:- Horizontal 3.0 metres Vertical 4.0 metres Vertical (Twin) 20.0 metres 4. Any additional “in line” bends in the flue system must be taken into consideration. Their equivalent lengths are:- Concentric Pipes: 45° bend 0.5 metres 90° bend 1.0 metres Twin Flue Pipes Air Duct Flue Duct 45° bend 1.3 metres 3.3 metres 90° bend 4.8 metres 12.0 metres 5. The illustrations opposite show examples of maximum equivalent lengths. 6. Full details of part numbers and descriptions of all optional flue components and kits can be found in Baxi Gas Central Heating Boilers Installers’ Guide. 7. Instructions for guidance and fitting are included in each kit. IMPORTANT: Solo 3 30 PF models must not be set at minimum input when installed with vertical flue systems. Horizontal Flues Vertical Flues Vertical Flues (Twin Pipe) Maximum Length = 2m inc. 2 x 45° bends Maximum Length = 21m inc. 4 x 45° bends Maximum Length = 2m inc. 2 x 90° bends
Страница 13 PDF
Страница 14
5.0 Installation 14 5.1 Initial Preparation 1. Unpack contents of carton. 2. Remove the lower door panel from the outer case. Remove the 2 screws holding the outer case to the combustion box. 3. Place the ready assembled outer case in a safe place until required. 4. Release the R clip from the top latch securing the combustion box to the back plate and release both latches (Fig. 14). 5. Lift and remove the combustion box from the back plate (Fig. 15). Place the combustion box on its back. IMPORTANT - When installing a Solo 3 with a rear flue see section 5.2 before continuing the installation. 6. Proceed to the relevant section for flueing the appliance either to the Rear, Left, Right or Vertically. NOTE: For Vertical flueing or flue lengths greater than standard, the relevant optional extra kits must be obtained and their instructions followed. Fig. 14 Fig. 15
Страница 14 PDF
Страница 15
5.0 Installation 15 5.2 Fan Outlet Restrictor (30, 40, 50, 60, 70 and 80) Rear Flue only up to 500mm (195/8 in) 1. Release the four latches holding the combustion box door (Fig 18). Remove the combustion box door by pulling forward (Fig. 16). 2. Release the 5-pin electrical plug connecting the pressure switch and fan (Fig. 17). Withdraw the fan assembly by pulling forwards from the top edge (Fig. 16). 3. Take the sheetmetal restrictor (supplied in the kit of parts), check that the number stamped on the restrictor matches the appliance (e.g. 50 stamped on the restrictor is for 50 PF appliance) 4. Fit the restrictor to the fan outlet flange, bending the 3 lugs equally ensuring the restrictor seals against the fan outlet flange (Fig. 19). 5. Re-assemble the fan assembly and combustion box door ensuring that the flexible tubes from the fan unit to the pressure switch are routed correctly and that they are not kinked or flattened (Fig. 19a). Fan Outlet Flange Fan Outlet Restrictor Fig. 17 Fig. 18 Fig. 16 Fig. 19 Flexible Tubes Fig. 19a
Страница 15 PDF
Страница 16
5.0 Installation 16 5.3 Position the Boiler 1. Choose a suitable position for the boiler making necessary allowances for the minimum clearances required (see page 10). 2. Hold the wall template against the wall at the required boiler location. Ensure that the top of the template is level (Fig. 20). 3. The template represents the outer limits of the appliance plus the required minimum side clearance. 4. Mark the position of the flue hole centre and the inward pointing corners of the two triangular cutouts in the template. Mark the position of the four fixing holes. Where possible use the uppermost and lowest fixing hole positions, otherwise space the fixing holes as far apart as possible (Fig. 20). 5.4 Rear Flue Concentric flue kits are available to allow 3 metres horizontal and 4 metres vertical flueing. Twin flue at 80mm diameter will allow up to 15 metres vertical flueing. 1. For installations where the flue terminal is inaccessible from the outside, an internal fitting kit is available. This can be obtained from your local merchant quoting Baxi Part No 236441. 2. If using the internal fitting kit a 117mm (45/8 in) diameter hole is required. 3. Drill the anchorage holes 63mm (21/2 in) deep to accept suitable wall plugs (Fig. 21). 4. Using the previously marked flue hole centre, cut a hole approximately 107mm (41/4 in) diameter in the masonry for the 100mm (4 in) diameter flue duct. (When using a core drill, it is important to keep the drill level and square). Fig. 20 Fig. 21
Страница 16 PDF
Страница 17
5.0 Installation 17 5.5 Rear Flue Preparation Wall thickness 285mm - 500mm (115/16 - 193/8) go to section 5.6. Wall thickness 100mm - 284mm (4 in - 113/16 in). If the wall thickness is less than 285mm (113/16 in), it will be necessary to cut the components of the flue to the appropriate size. 1. Measure the wall thickness (Fig. 22). Mark this dimension on the Flue Duct from the flared end and cut the waste off the plain end (Fig. 23). 2. Take the Flue Terminal Assembly and measure from the terminal end the wall thickness and subtract 40mm (Fig. 23a). Cut the waste off the plain end. Wall Thickness - 40mm (all boilers) 3. The cardboard support should be installed onto the flue tubes to ensure the assembly is supported during cutting (Fig. 25 & 26). 4. Measure the same amount from the flange end of the Air Duct and cut the waste off the plain end (Fig. 24). Wall Thickness - 40mm (all boilers) 5. Go to section 5.6. Wall Thickness Fig. 23 Fig. 23a Fig. 24 Fig. 25 Fig. 26 Fig. 22 Waste Wall Thickness Flue Duct Waste Wall Thickness - 40mm Wall Thickness - 40mm Waste Cardboard Support Cut Line Flue Terminal Assembly Air Duct Cardboard Support
Страница 17 PDF
Страница 18
5.0 Installation 18 5.6 Assembly of Rear Flue 1. Remove the rear air box blanking plate from the back plate by releasing the three screws (Fig. 27). 2. Remove the blanking cap at the rear of the turret, by pushing and turning anti-clockwise to release the bayonet fitting (Fig. 27). 3. Locate the flared end of the flue duct over the bayonet fitting on the turret, taking care not to damage the 'O' ring. Lock the flue duct in place by pressing in and turning clockwise (Fig. 28). 4. Engage the bayonet slots of the air duct over the location lugs on the back plate opening and press and turn clockwise to secure the air duct to the back plate (Fig. 29). 5. In order to increase security of the flue, the bayonet tags may be deformed to secure the flue in position. 6. Take the flue terminal assembly and engage on the flue and air ducts. Slide the flues together to the desired wall thickness. 7. Tape the sections of the outer ducts together with the tape provided ensuring a good seal is made (Fig. 30). Fig. 27 Fig. 28 Fig. 29 Flue Duct Air Duct Tape Fig. 30 Air Box Blanking Plate Blanking Cap Backplate
Страница 18 PDF
Страница 19
5.0 Installation 19 5.7 Fitting the Back Plate 1. Engage the assembly into the hole previously cut in the wall and slide in place (Fig. 31). 2. Secure the assembly to the wall at the previously drilled anchorage points with suitable screws (Fig. 31). Before finally tightening the screws, check that the assembly is level. 3. Make good between the wall and the air duct outside the building if the internal fitting kit has not been used (Fig. 32). 4. The flue trim provided may be fitted if required, to neaten the make-up around the terminal (Fig. 33). 5. To fit the flue terminal trim: a) The trim should be fitted once the flue is secure. b) Take the three edge clips from the kit and fit them equi-spaced onto the inner flange of the trim (Fig. 32a). c) With the flanges towards the wall pass the trim over the terminal. If required a bead of sealant may be applied to the rear face of the trim. d) Push firmly on the trim to ensure the edge clips engage on the flue. Fig. 31 Fig. 33 Fig. 32 Edge Clip Flue Trim Flue Trim Fig. 32a
Страница 19 PDF
Страница 20
5.0 Installation 20 5.8 Left or Right Flue Concentric flue kits are available to allow 3 metres horizontal and 4 metres vertical flueing. Twin flue at 80mm diameter will allow up to 15 metres vertical flueing. NOTE: If the flue terminal is inaccessible from outside the building, it is necessary to fix the internal fitting kit in position before continuing with the installation. (See section 5.15 Internal Fitting Kit of these instructions). 1. The procedure for fitting the appliance flued to the left or right hand side is the same. 2. 30-40-50 PF - Left/Right Hand Side maximum flue 410mm (16 in). 3. 60-70-80 PF - Left/Right Hand Side maximum flue 355mm (14 in). 4. Using the previously marked flue hole centre (Section 5.3) and the two marks made at the triangular cutouts of the template, mark the horizontal centre line for the flue assembly (Fig. 34). 5. Extend this line either left or right as required, to the corner of the room (Fig. 34). 6. Extend the horizontal centre line around the corner for approximately 300mm (12 in). Ensure that the line remains horizontal by checking with a spirit level (Fig. 35). 7. From the wall template cut out the ‘D’ shaped section. Using this as a template, line up the horizontal triangular cut outs with the extended 300mm (12 in) line and make sure that the flat of the template is butted up against the corner of the wall (Fig. 36). 8. If the appliance mounting wall is out of true, use string or a straight edge to determine the true corner position and mark a vertical line to accommodate the flat edge of the template. 9. Holding the template firmly, mark the vertical centre line for the flue assembly by marking the point at the outer corners of the upper and lower cut outs (Fig. 37). 10. Remove the template and draw a vertical line between the two marks. The intersection of the vertical and horizontal lines is the centre of the flue hole (Fig. 38). 11. If using the internal fitting kit a 117mm (45/8 in) diameter hole is required. 12. Cut a hole approximately 107mm (41/4 in) diameter in the masonry for the 100mm (4 in) diameter flue duct (Fig. 39). (Use of a core drill is recommended. When using a core drill, it is important to keep the drill level and square, particularly with the wall onto which the boiler is to be fitted). 13. Drill the anchorage holes 63mm (21/2 in) deep to accept suitable wall plugs. Fig. 34 Fig. 35 Fig. 36 Fig. 37 Fig. 38 Fig. 39 Maximum lengths for side flues using the standard telescopic flue kit 410mm (30, 40, 50) 410mm (30, 40, 50) 355mm (60, 70, 80) 355mm (60, 70, 80)
Страница 20 PDF
Страница 21
90mm (30/40/50 PF) 145mm (60/70/80 PF) 5.0 Installation 21 5.9 Side Flue Preparation 1. For both Left and Right Hand Flue - Measure the distance from the wall to the nearest line marked from the template. This will be known as dimension X (Fig. 40). 2. Measure the thickness of the wall from the inside. This will be known as Wall Thickness (Fig 41). 3. To make up the total flue length, add 90mm (30/40/50 PF) or 145mm (60/70/80 PF) to the Wall Thickness + X dimension: Total flue length = Wall Thickness + X + 90mm (30/40/50 PF) Wall Thickness + X + 145mm (60/70/80 PF). NOTE: if total calculated flue length exceeds 500mm (195/8 in), a flue extension kit will be required. CUTTING THE FLUE NOTE: If Wall Thickness + X is less than; 195mm (PF 50-40-30) or 140mm (PF 80-70-60), it will be necessary to cut the components of the flue to make up the appropriate size. 4. Take the Flue Duct and measure the dimension below from the flared end. Cut the waste off the plain end (Fig. 42). Wall Thickness + X + 90mm (30-40-50 PF) Wall Thickness + X + 145mm (60-70-80 PF) 5. Take the Flue Terminal Assembly and measure from the terminal end the dimension below (Fig. 43). Cut the waste off the plain end. Wall Thickness + X + 50mm (30-40-50 PF) Wall Thickness + X + 105mm (60-70-80 PF) 6. Measure the same amount from the flange end of the Air Duct and cut the waste off the plain end (Fig. 43a). Wall Thickness +X + 50mm (30-40-50 PF) Wall Thickness + X + 105mm (60-70-80 PF) 7. The cardboard support supplied in the flue pack should be installed onto the flue tubes to ensure the assembly is supported during cutting (Fig. 44 & 45). Wall Thickness + X + 90mm (30/40/50) Wall Thickness + X + 145mm (60/70/80) Wall Thickness X Wall Thickness + X + 50mm (30/40/50) Wall Thickness + X + 105mm (60/70/80) Wall Thickness + X + 50mm (30/40/50) Wall Thickness + X + 105mm (60/70/80) Fig. 40 Fig. 41 Fig. 41a Fig. 42 Fig. 43 Fig. 43a Waste Flue Duct Flue Terminal Assembly Air Duct Wall Thickness X Total Flue Length Waste Waste Cardboard Support Cut Line Fig. 45 Fig. 44 Cardboard Support
Страница 21 PDF
Страница 22
5.0 Installation 22 5.10 Fitting the Flue and Back Plate 1. NOTE: There are two options for fitting the flue and back plate they are: Method A - Fitting the flue and back plate as an assembly (usually used where there are no side clearance problems). Method B - Pre-fitting the flue through the wall, fitting the back plate to its position on the wall and then connecting the two together (usually used where side clearances are restrictive). 5.11 Method A 1. Remove the left or right hand air box blanking plate, as appropriate, from the back plate air box by releasing the three screws (Fig 46). 2. Rotate the turret to face the selected opening (Fig. 47) and remove the side blanking cap by pushing in and turning anti-clockwise to release the bayonet fitting (Fig. 46). 3. Locate the flared end of the flue duct over the bayonet fitting on the turret, taking care not to damage the 'O' ring. Lock the flue in place by pressing in and turning clockwise (Fig. 49). 4. Ensure that the 'O' ring seal is in position against the sealing flange. 5. Fit the air duct over the flue duct and draw towards the air box on the back plate. Engage the bayonet slots of the air duct over the location lugs of the back plate opening and press and turn clockwise to secure the air duct to the air box (Fig. 50). 6. In order to increase security of the flue, the bayonet tags may be deformed to secure the flue in position. 7. Take the flue terminal assembly and engage on the flue and air ducts. Slide the flues together to the desired flue length. Tape the outer duct sections together with the tape provided ensuring a good seal is made. Fig. 46 Fig. 47 Fig. 49 Fig. 50 Turret Air Box Blanking Plate Blanking Cap Flue Duct Air Duct
Страница 22 PDF
Страница 23
5.0 Installation 23 5.11 Method A (Cont) 7. Engage the assembly into the hole previously cut in the wall and slide into place. 8. Secure the assembly to the wall at the previously drilled anchorage points with suitable screws. Before finally tightening the screws, check that the assembly is level (Fig. 51). 9. Make good between the wall and the air duct inside and outside the building if the internal fitting kit has not been used (Fig. 52). 10. The flue trim provided may be fitted if required, to neaten the make-up around the terminal (Fig. 53). 11. To fit the flue terminal trim: a) The trim should be fitted once the flue is secure. b) Take the three edge clips from the kit and fit them equi-spaced onto the inner flange of the trim (Fig. 52a). c) With the flanges towards the wall pass the trim over the terminal. If required a bead of sealant may be applied to the rear face of the trim. d) Push firmly on the trim to ensure the edge clips engage on the flue. Fig. 53 Fig. 51 Fig. 52 Edge Clip Flue Trim Flue Trim Fig. 52a
Страница 23 PDF
Страница 24
5.0 Installation 24 5.12 Method B 1. Remove the left or right hand air box blanking plate, as appropriate, from the back plate air box by releasing the three screws (Fig. 54). 2. Rotate the turret to face the selected opening (Fig. 55) and remove the side blanking cap by pushing in and turning anti-clockwise to release the bayonet fitting (Fig. 54). 3.Locate the flared end of the flue duct over the bayonet fitting on the turret, taking care not to damage the ‘O’ ring. Lock the flue duct in place by pressing in and turning clockwise (Fig. 57). 4. Engage the bayonet slots of the air duct over the location lugs on the back plate opening and press and turn clockwise to secure the air duct to the back plate (Fig. 58). 5. Engage the flue and air ducts into the hole previously cut in the wall and through holes in other partitions (cupboards, walls etc.). 6. Secure the back plate to the wall at the previously drilled anchorage points with suitable screws. Before finally tightening the screws, check that the assembly is level. 7. Take the flue terminal assembly and pass through the cut hole from outside. Engage on the flue and air ducts. Slide the flues together to the desired wall thickness, tape the outer duct sections together with the tape provided ensuring a good seal is made. 8. In order to increase security of the flue, the bayonet tags may be deformed to secure the flue in position. 9. Make good between the wall and the air duct inside and outside the building if the internal fitting kit has not been used (Fig. 59). 10. The flue trim provided may be fitted if required, to neaten up the make-up around the terminal (Fig. 60). 5. To fit the flue terminal trim: a) The trim should be fitted once the flue is secure. b) Take the three edge clips from the kit and fit them equi-spaced onto the inner flange of the trim (Fig. 59a). c) With the flanges towards the wall pass the trim over the terminal. If required a bead of sealant may be applied to the rear face of the trim. d) Push firmly on the trim to ensure the edge clips engage on the flue. Fig. 55 Fig. 54 Turret Fig. 60 Fig. 59 Fig. 57 Fig. 58 Flue Duct Air Duct Air Box Blanking Plate Blanking Cap Edge Clip Flue Trim Flue Trim Fig. 59a
Страница 24 PDF
Страница 25
5.0 Installation 25 5.13 Terminal Guard 1. When codes of practice dictate the use of terminal guards, they can be obtained from most plumbers and builders merchants nationwide. 2. When ordering a terminal guard, quote the appliance name and model number. 3. There must be a clearance of at least 50mm between any part of the terminal and the guard. 5.14 Fitting a Terminal Guard (Fig. 61) 1. Position the guard over the terminal on the outside wall. Ensure the guard is equally spaced about the terminal. Mark the fixing positions. 2. Drill and plug fixing the positions then secure the guard to wall. Fig. 61
Страница 25 PDF
Страница 26
5.0 Installation 26 5.15 Internal Fitting Kit 1. The internal fitting kit (available from merchants free of charge quoting Baxi Part No. 236441) is suitable for walls between 100mm (4in) and 285mm (113/16in) in thickness. 2. TO INSTALL THE KIT - Mark the flue hole centre as described in section 5.4 or 5.8. Cut a hole in the masonry approximately 117mm (45/8 in) diameter for the internal fitting kit. The use of a core drill is recommended. (When using a core drill, it is important to keep the drill level and square). 3. Measure the wall thickness and from this dimension subtract 10mm (3/8 in) (Fig. 62). 4. Remove the wall liner from its packing and remove the end piece (Fig. 63). 5. Mark off the dimension, wall thickness - 10mm (3/8 in), measuring from the beaded end of the duct and cut off the remaining length of the duct. Ensure that the cut is square and reasonably straight (Fig. 64). Wall Thickness - 10 Wall Thickness Fig. 62 Fig. 63 Fig. 64
Страница 26 PDF
Страница 27
5.0 Installation 27 5.15 Internal Fitting Kit (Cont) 6. Refit the end piece to the liner and open out to the thickness of the wall. Seal the two pieces together using the tape provided with the kit (Fig 65). 7. Slide the assembled wall liner into the hole in the wall until the tags stop against the inner wall with the seam of the liner uppermost. Mark the positions of the holes in the tags on the wall and then rotate liner so that tags reveal marks (Fig. 66). 8. Drill and plug the wall in these positions (Fig. 67). 9. Rotate liner back until the tags align with the holes drilled and secure it to the wall using suitable screws (Fig. 68). 10. Make good between the edge of the liner and the outside wall with cement mortar or a similar substance, by reaching through the liner and pressing the mortar between liner and the outside brick work (Fig. 69). Make good between the liner and the inside wall. Apply soap solution to the ‘O’ ring inside the liner. 11. The rest of the installation may now proceed as described. Fig. 65 Fig. 66 Fig. 67 Fig. 68 Fig. 69
Страница 27 PDF
Страница 28
5.0 Installation 28 5.16 Fitting the Combustion Box 1. Offer up the combustion box to the back plate and locate the rear bottom edge of the combustion box onto the self locating support at the base of the wall plate (Fig. 70). 2. Swing the top of the combustion box backwards against the top air box (Fig. 71). 3. Engage the two retaining latches and secure with the 'R' clip previously removed (Fig. 72). Fig. 71 Fig. 70 Fig. 72
Страница 28 PDF
Страница 29
5.0 Installation 29 NOTE: The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance. Connection may be made via a fused double pole isolator with a contact separation of at least 3mm (1/8 in) in all poles and serving the appliance and system controls only. All cables should be routed to avoid hot surfaces. WARNING - THIS APPLIANCE MUST BE EARTHED. 4 core input cable for connection to the appliance must be not less than 0.75mm2 (24 x 0.2mm) PVC grade to IEC 227 code 53 (heat resisting). External controls and the appliance MUST be supplied via the same isolator. NOTE: Polarity of the appliance MUST be correct otherwise the appliance will not operate correctly. or b r g/y w br b gy bk w y y or/bk y/r y/bk r/b or or g w bk gy br b Pump N Main Gas Valve Pilot Gas Valve Fan Pressure Switch Thermostat Sensor Overheat Thermostat Control Potentiometer & Switch Spark Electrode N N N External Controls S/L L 230V L b r b or b br gy w y bk y or or or/bk or/bk r/b y/bk y/r w PCB Schematic Wiring Diagram Pressure Switch Overheat Thermostat Control Potentiometer & Switch Thermostat Sensor Spark Electrode Fan Gas Valve Key br - brown b - blue r - red w - white bk - black or - orange gy - grey y - yellow g - green g/y - green & yellow or/bk - orange & black r/b - red & blue y/bk - yellow & black y/r - yellow & red 5.17 Electrical Connections
Страница 29 PDF
Страница 30
5.0 Installation 30 5.18 Making the Electrical Connections 1. Remove the cover from the control box by removing the 2 screws (Fig. 73). 2. Slide the box forward for easier access. 3. The terminal strips may be removed by carefully pulling them forward. Connect the supply cable and the pump cable to the terminal strips (Fig. 75). IMPORTANT - When installing in conjunction with a thermal store or heat store please refer to the store manufacturers installation instructions when wiring the boiler. 4. The pump must be connected to the boiler terminals. 5. A permanent live must be connected to the 'L' terminal. 6. The switched live must be connected to the 'S/L' terminal. 7. Clamp the cables in the grips provided. Ensure that the lengths of the supply cables are such that the current carrying wires become taut before the earth wires if the cable should pull out of the cable clamp (Fig. 74). 8. Tuck the cables under the box and clip to the wall where necessary. Make sure sufficient slack is left to allow the box to slide forward for future access. 9. A cable clip is provided in the base of the box. Switched Live Permanent Live Neutral Earth Pump Earth Pump Neutral Pump Live Fig. 73 Fig. 74 Fig. 75
Страница 30 PDF
Страница 31
5.0 Installation 31 5.19 Water Connections 1. The boiler has two side water connections, the top connection being FLOW and the bottom connection being RETURN (Fig. 75a). 2. It is essential that FLOW and RETURN pipes are connected to the correct fittings. 3. The top flow connection incorporates the boiler thermostat and overheat thermostat (Fig. 76). 4. A copper elbow, compression nut and olive are provided in the kit for the return connection. NOTE: Drain cocks should be fitted to all the system's low points. 5. Take the boiler thermostat assembly and the overheat thermostat and clip from the kit. • Clip the boiler thermostat to the flow pipe adjacent to the elbow. • Engage the overheat thermostat in the clip and fit to the flow pipe next to the boiler thermostat. • Take the cable tie from the kit and use it to secure the overheat thermostat clip. The cable tie must be fitted diagonally so that it sits at both sides of the ribs on the clip. • Connect the electrical tags to the thermostats. The overheat thermostat has the larger terminals. • The thermostats have no polarity - either tag can go on either terminal. • Ensure that the area of the flow pipe to which the thermostats are fitted is free of excess solder and debris. 5.20 Pipe Routes 1. Ensure that any pipework is routed so as to leave the boiler via the spaces at the rear of the outer case, either at the top or at the bottom. 2. Pipes may be dropped down within the outer case in the spaces between the back plate and the combustion box. NOTE: It is important that the pipework does not interfere with the correct fitting of the outer case and a space of 14mm clearance must be left between any vertical pipes and the outer sides of the back plate. 5.21 Gas Connection 1. Connection to the gas supply is RC1/2 (1/2 in BSPT internal) located at the rear of the gas cock (Fig. 78). 2. When connecting the gas feed pipe, the control box may be pulled forward to give greater access. Fig. 75a Fig. 78 Fig. 76 Overheat Thermostat Flow Pipe Thermostat Sensor Orange Leads Cable Tie Fig. 77 Yellow Leads
Страница 31 PDF
Страница 32
6.0 Commissioning the Appliance 32 6.1 Commissioning the Appliance 1. Flush the whole system in accordance with BS 5793 (see Section 3.1 Water Circulating Systems). Check for water leaks. 2. Purge away air from the supply pipe at the gas service cock. (BS 6891) (Fig. 79). 3. Ensure that the electrical supply is isolated. 4. Check the electrical supply for earth continuity, polarity, short circuit and resistance to earth. 5. Turn the gas service cock anti-clockwise to the ON position and check for gas soundness up to the gas valve. 6. Loosen the pressure test point screw on the right hand side of the gas control valve (there is no need to completely remove this screw to obtain a pressure reading) and connect a pressure gauge. 7. Turn the boiler thermostat control knob fully anti-clockwise to the OFF position marked 0 (Fig. 80). 8. Ensure that the electricity supply is turned ON and set any external controls to the ON position. 9. Turn the boiler thermostat knob fully clockwise. 10. The fan will start running and after approximately 10 seconds, the ignition spark will commence. 11. The sparking will continue until the pilot light is established (Fig. 81) and then the main burner will light from the pilot flame. 12. Check that both the main burner and the pilot are alight by observing through the viewing window. The indicator lights should also be illuminated. 13. Should this sequence not occur, then refer to the fault finding section of these instructions. NOTE: The pilot rate for this appliance is factory set, sealed and therefore non- adjustable. * Overheat Boiler On Fan On Pilot On Burner On Overheat Neon Warning 17 3 Fig. 79 Fig. 80 Fig. 81
Страница 32 PDF
Страница 33
6.0 Commissioning the Appliance 33 6.1 Commissioning the Appliance (Cont) 1. From the table opposite check that the main burner pressure is correct after the appliance has been running for 10 minutes. 2. Check for gas soundness, with main burner alight, using leak detection fluid. 3. If necessary, adjustment to main burner pressure can be made by altering the regulator as shown (Fig. 82). 4. To alter the burner pressure, turn the adjustment screw in either direction until the required pressure is obtained. 5. Turn the boiler thermostat to the OFF position marked 0. Screw home the pressure test point screw. Turn the boiler thermostat knob to the required setting. 6. The boiler and system should be run and then flushed and treated in accordance with BS 7593:1992 and the flushing agent / inhibitor manufacturers instructions. When all the air has been removed from the water circuit, the pump and radiators should be balanced to achieve the design temperature drop across the system. 7. Make a final check for gas soundness and set any timer control, room thermostats etc. to the customer's specific requirements. 8. The boiler is protected by an integral frost-stat, but if the boiler is not to be used for a long period of time, the system should be drained. NOTE: The frost thermostat operates even if the boiler thermostat is in the OFF position and it is necessary therefore, if the system is drained, for the external electrical and gas supplies to be isolated. It is recommended that a label be affixed to the appliance to draw attention to the fact that the system has been drained. WARNING - If the system is filled with very cold water and the boiler lit, the action of the frost protection thermostat will prevent the boiler from shutting down before the water temperature reaches 10°C. 9. Carefully read and complete all sections of the “Benchmark” Installation, Commissioning and Service Record Log Book that are relevant to the appliance and installation. The details of the Log Book will be required in the event of any warranty work. The Log Book must be handed to the user for safe keeping and each subsequent regular service visit recorded. Model Input P Setting Pressure kW Btu/h mbar in wg 30 Maximum 10.99 37, 500 16.0 + 0.5 6.4 + 0.2 Minimum 7.33 25, 000 8.0 + 0.5 3.2 + 0.2 40 Maximum 14.65 50, 000 16.0 + 0.5 6.4 + 0.2 Minimum 11.36 38, 750 10.0 + 0.5 4.0 + 0.2 50 Maximum 18.32 62, 500 16.0 + 0.5 6.4 + 0.2 Minimum 15.02 51, 250 11.5 + 0.5 4.4 + 0.2 60 Maximum 21.98 75, 000 16.0 + 0.5 6.4 + 0.2 Minimum 18.68 63, 750 11.5 + 0.5 4.4 + 0.2 70 Maximum 25.64 87, 500 16.0 + 0.5 6.4 + 0.2 Minimum 22.35 76, 250 12.16 + 0.5 4.8 + 0.2 80 Maximum 29.31 100, 000 16.0 + 0.5 6.4 + 0.2 Minimum 26.01 88, 750 9.5 + 0.5 3.8 + 0.2 Burner Pressure Test Point Regulator Fig. 82 IMPORTANT: Solo 3 30 PF models must not be set at minimum input when installed with vertical flue systems.
Страница 33 PDF
Страница 34
7.0 Fitting the Outercase 34 7.1 Fitting the Outercase 1. The warning label may be removed unless the boiler is to be fitted within a cupboard. 2. Taking the ready assembled outercase, the front door of which has already been removed, proceed as follows: 3. If the appliance is flued to the left or to the right, remove the relevant infill panel by removing the retaining clips and fixing screws (Fig. 83). 4. Offer the outer case up to the hooks on the top of the back plate (Fig. 85). 5. Ensure that the outer case is located over the lower tabs on the back plate on both sides (Fig. 86). 6. Using the two screws previously removed, secure the outer case to the combustion box (Fig. 84). 7. Replace the lower front door panel. 8. Instruct the user in the operation of the boiler controls. Hand over the Users Operating, Installation and Servicing Instructions and the Log Book giving advice on the necessity of regular servicing. Fig. 83 Fig. 84 Fig. 85 Fig. 86 Infill Panel
Страница 34 PDF
Страница 35
8.0 Overheat Cut-off Device 35 8.1 Operation 1. The overheat cut-off device is of the manual reset type and therefore it is important that the user knows how to reset the control should it ever cut out. NOTE: Cut-out is indicated by illumination of the neon light on the control box. 2. Remove the lower door panel by following the sequence of diagrams (Fig 87). 3. To reset the boiler - Turn the boiler thermostat control knob fully anti-clockwise to the OFF position marked ‘0’ (Fig. 88). Wait ten seconds, turn the control knob clockwise to the required thermostat setting, the red neon goes out, the boiler will start automatically. 4. No adjustment to the gas controls or main thermostat are required. 5. If the overheat thermostat drops out repeatedly, refer to the fault finding chart at the rear of this booklet or consult a competent service engineer. Fig. 87 Fig. 88 1 2 3 * Overheat Boiler On Fan On Pilot On Burner On Overheat Neon Warning
Страница 35 PDF
Страница 36
9.0 Annual Servicing 36 9.1 Dismantling the Boiler 1. To ensure its continued safe and efficient operation, it is important that the appliance is regularly serviced. ( For location of British Gas service test point see Changing Components section of these instructions). 2. Before servicing the boiler please read Section 1.3 Important Information. 3. After servicing, complete the relevant section of the “Benchmark” Installation, Commissioning and Service Record Log Book. This should be in the possession of the user. 4. Isolate the electrical supply to the boiler. 5. Remove the outer case lower door panel by following the sequence of diagrams (Fig. 89). 6. Remove the outer case from the boiler by unscrewing the two screws and lift the case clear (Fig. 90). 7. Release the four latches holding the combustion box door (Fig. 91). Remove the combustion box door by pulling forward (Fig. 93). 8. Release the 5-pin electrical plug connecting the pressure switch and fan (Fig. 92). Withdraw the fan assembly by pulling forwards from the top edge (Fig. 93). Fig. 89 Fig. 90 Fig. 91 Fig. 92 Fig. 93 1 2 3
Страница 36 PDF
Страница 37
9.0 Annual Servicing 37 9.2 Cleaning the Combustion Box 1. Remove the burner assembly by pulling it forward (Fig. 94). 2. Lightly brush any dirt from the top of the burner blades and ensure that the ports are free from obstruction. 3. Remove the baffle retension clip (Fig. 93a). 4. Lift the baffles out of the heat exchanger (Fig. 94). 9.3 Cleaning the Heat Exchanger 1. The heat exchanger may be cleaned by insertion of a thin metal strip e.g. a hack saw blade or steel rule, from above or below, taking care not to damage any insulation. 2. Clean the front and rear fin sections and ensure that any blockages are cleared. 9.4 Cleaning the Burner Injector 1. Remove the injector which is screwed into the burner feed manifold (Fig. 95). 2. Examine and clean carefully, then replace ensuring that the copper washer is in position. Tighten the injector fully. 9.5 Cleaning the Pilot 1. Disconnect the spark electrode lead at the electrode (Fig. 96). 2. Unscrew the electrode from the manifold and withdraw the electrode (Fig. 96). 3. Remove the right hand side insulation carrier bracket by releasing the screw. Remove the side insulation (Fig. 94). 4. Release the screw securing the pilot hood and remove (Fig. 96a). 5. Carefully remove the pilot injector (Fig. 96a). Examine and clean it as necessary. Do not use a wire or pin to clean the injector orifice. 6. Examine the sealing washer (Fig. 96a) and replace if it is damaged in any way. Reassemble in reverse order. 7. Replace all components in reverse order ensuring that the flexible tubes from the fan unit to the pressure switch are routed correctly and that they are not kinked or flattened (96b). 8. Check that the seal to the combustion box door is good. 9. Re-commission the boiler before use, checking for gas soundness and ensuring all controls are working correctly. 10. Complete the relevant section of the “Benchmark” Installation, Commissioning and Service Record Log Book and hand it back to the user. 60, 70 & 80 PF Models Only Fig. 94 Fig. 93a Fig. 95 Fig. 96 Fig.96a Pilot Hood Pilot Injector Sealing Washer Electrode Baffles Baffle Retension Clip Flexible Tubes Fig. 96b
Страница 37 PDF
Страница 38
10.0 Changing Components 38 Centre Pin Retaining Rivet Fig. 98 Fig. 99 Fig. 100 Fig. 101 Fig. 102 Fig. 103 10.1 Changing Components 1. When changing components ensure that the gas and electrical supplies are isolated before the work is started. 2. Before changing any components please read Section 1.3 Important Information. 3. Remove the outer case lower door panel (Fig. 98). 4. Remove the outer case from the boiler by unscrewing the two screws and lift the case clear (Fig 99). 10.2 Replacing the Circuit Board 1. Ensure that the electrical supply is isolated. 2. Remove the cover from the front of the controls box (Fig. 100). 3. Release the mains cables from the cable clamps and unplug the mains connection blocks from the circuit board (Fig. 101). 4. Remove the screw retaining the thermostat control panel and slide the circuit board from the box. 5. Carefully withdraw the centre pin from the retaining rivet which then allows the retaining rivet to be removed. Remove the thermostat control panel (Fig. 102). (On reassembling ensure the control panel is located over the retaining rivet body before inserting the centre pin.) 6. Disconnect the plugs from the sockets on the circuit board (Fig. 103). 7. Replace new circuit board in reverse order checking that the connections are correct as shown in the diagram (See Electrical Connections section 5.17 of these instructions) and that the harness is retained in the strain reliefs. 1 2 3 British Gas Service Test Point. For use by B.G. Personnel only
Страница 38 PDF
Страница 39
10.0 Changing Components 39 10.3 Ignition Electrode (Fig. 104) 1. Disconnect the spark electrode lead at the electrode. 2. Unscrew the electrode from the manifold and withdraw the electrode. 3. Replace the new electrode in reverse order, ensuring that the sleeving is pushed over the end of the electrode. 10.4 Gas Valve (Fig. 105) 1. Disconnect the inlet gas cock union. 2. Remove the cover from the front face of the gas valve and remove the electrical connections from the tags on the gas valve. 3. Disconnect the gas valve by unscrewing the three screws on the top face of the gas manifold. If access to these screws is dificult the valve can be removed with the manifold. 4. Remove the gas valve being careful not to damage the gasket. 5. Fit the new gas valve by re-assembling all components in reverse order, ensuring that the gasket is properly positioned. 10.5 Thermostat Sensor (Fig. 106) 1. Disconnect the two electrical tags from the sensor. 2. Prise the clip and sensor off the flow manifold. 3. Clip the new sensor to the manifold and reconnect the wires. Either wire can be connected to either spade terminal - there is no polarity. 10.6 Over-Heat Thermostat (Figs.106 & 107) 1. Disconnect the two electrical tags from the overheat thermostat. 2. Cut off the cable tie securing the clip to the pipe. 3. Prise the clip and thermostat from the pipe, noting its position. Disengage the thermostat from the clip. 4. Engage the new thermostat in the clip. Prise the clip over the flow pipe ensuring it is positioned as previously. Take the cable tie supplied with the new overheat thermostat and use it to secure the clip. The cable tie must be fitted diagonally so that it sits at both sides of the ribs on the clip. 5. Connect the two electrical tags to the terminals on the overheat thermostat - either wire can be connected onto either terminal - there is no polarity. Fig. 104 Fig. 105 Electrode Fig. 106 Fig. 107 Overheat Thermostat Flow Pipe Thermostat Sensor Orange Leads Yellow Leads Cable Tie British Gas Service Test Point. For use by B.G. Personnel only
Страница 39 PDF
Страница 40
10.0 Changing Components 40 10.7 Changing Components (Cont) 1. To change Fan - Pressure Switch - Burner - Burner Injector - Pilot Burner Injector - Gas Manifold, proceed as follows:- 2. Release the four latches holding the combustion box door (Fig. 108). Remove the combustion box door by pulling forward (Fig. 110). 3. Release the 5-pin electrical plug connecting the pressure switch and fan (Fig. 109). Withdraw the fan assembly by pulling forwards from the top edge (Fig. 110). 10.8 Fan (Fig. 111) 1. Disconnect the two sensing tubes from the venturi situated on the fan. 2. Disconnect the 2 fan wires from the connection on the electrical plug. Remove the 3 screws securing the fan to the fan hood. 3. 30-40-50 models only - Remove the two screws securing the fan outlet flange to the fan and remove. Clean all sealing mastic from the outlet flange. 4. Fit the outlet flange onto the new fan, fix with the 2 screws and seal the outside gap between the fan body and the outlet fan with the mastic provided. 5. 60-70-80 models only - When fitted, unbend the tabs securing the fan outlet restrictor to the outlet flange on the original fan. 6. Fit the outlet restrictor to the new fan outlet flange. Bend the tabs over the flange to secure the restrictor. 7. Fit the new fan and re-assemble all components in reverse order of dismantling, reconnect the new fan wires into the connections on the electrical plug - either wire can be connected into either connection. 10.9 Pressure Switch (Fig. 112) 1. Disconnect sensing tubes noting their positions. 2. Remove the screw securing the pressure switch to its bracket and unhook the pressure switch. 3. Disconnect the 3 electrical terminals from the pressure switch. Note the position of the tags before removal and reconnect in correct order. 4. Fit new pressure switch and re-assemble all components ensuring that the flexible tubes from the fan unit to the pressure switch are routed correctly and that they are not kinked or flattened (Fig. 112b). Ensure that the electrical terminals are connected to their correspondingly marked tags. Fig. 108 Fig. 110 Fig. 111 Fig. 112 Outlet Flange (30-40-50 Models shown) Green Fan Fig. 109 Sensing Tubes Black White Flexible Tubes Fig. 112b
Страница 40 PDF
Страница 41
10.0 Changing Components 41 10.10 Burner (Fig. 113) 1. Remove the burner assembly by pulling it forward. 2. Fit new burner and re-assemble all components in reverse order of dismantling. 10.11 Burner Injector (Fig. 114) 1. Release and remove the burner injector which is screwed into the burner feed manifold. 2. Fit the new burner injector ensuring that the copper washer is in position. Tighten the injector fully. 3. Re-assemble all components in reverse order. 10.12 Pilot Burner Injector (Fig. 115) 1. Remove the right hand side insulation carrier bracket by releasing the screw. Remove the side insulation panel. 2. Release the screw securing the pilot hood and remove. Carefully remove the pilot injector. Fit the new pilot injector ensuring the new sealing washer is in position. Tighten the injector fully. 3. Re-assemble all components in reverse order. 10.13 Gas Manifold (Fig. 116) 1. Remove the right hand side insulation carrier bracket by releasing the screw. Remove the side insulation panel (Fig. 113). 2. Remove the two screws securing the manifold from the inside of the combustion box and slide the manifold forward from under the two rear locating studs. 3. Remove valve and ancillary components from manifolds as necessary. 4. Replace all ancillary components onto manifold and replace manifold by sliding rear edge backwards under the two rear locating studs and securing from inside the combustion box using the two screws previously removed. Ensure that the sealing gasket is properly positioned and undamaged. 60, 70 & 80 PF Models Only Fig. 113 Fig. 114 Fig. 115 Fig. 116 Pilot Hood Pilot Injector Sealing Washer
Страница 41 PDF
Страница 42
11.0 Fault Finding 42 START Replace fan Replace harness Replace pressure switch Replace fan Replace thermostat Does fan run ? Is there a clear constant spark at the electrode ? Change potentiometer Is there mains voltage at S/L input ? Is there mains voltage at Pump L output ? Check fuse on circuit board Check pump wiring Note: This can occur if the boiler has overheated Reset by turning control knob OFF, wait 10 seconds then turn ON Does lockout light go out ? Is "Fan On" light on ? Check control knob is turned on Check that the wires are connected to the thermostat sensor Check that the fan & pressure switch plug is connected Is there continuity between C & NC terminals on the pressure switch ? Check pressure switch pipes for leaking or blockage Note: Under cold conditions fan run up time may exceed 1 min Ensure external controls are calling for heat Does pump run ? Is "Pilot On" light on ? Is lockout light on ? Is "Boiler On" light on ? Is there mains voltage at P/L input ? Is there mains at the fan connection ? Is there continuity across the overheat thermostat ? YES NO YES YES YES YES YES NO YES YES NO NO NO NO NO YES YES YES NO NO NO NO YES NO No continuity - change sensor Check continuity across pilot solenoid (1.5 K OHM) No continuity - change pilot solenoid Check continuity across sensor (1 M OHM at 20oC) Investigate pump Change PCB No continuity across fuse, change fuse YES YES Change PCB Check & clean electrode. Check gap & lead YES Check external wiring NO Check Potentiometer (see table) Before starting FAULT FINDING carry out preliminary electrical system checks i.e. Earth Continuity, Polarity, Short Circuit and Resistance to Earth.
Страница 42 PDF
Страница 43
11.0 Fault Finding 43 Replace the gas valve Replace PCB Boiler satisfactory Set pressure regulator Does the pilot burner light ? Does the main burner light ? Does the boiler shut down when the water flow reaches 80-84oC ? Does pump run on ? Is "Burner On" light on ? Are live & neutral reversed ? Indicator light inside box will be lit Check pilot flame for correct size Check & clean electrode. Check spark gap. Check electrode lead Check there is 20mbar gas pressure at the inlet to gas valve Check there is 20mbar gas pressure at the inlet to gas valve Check the pilot injector is not blocked, partially blocked or damaged Check there is 20mbar gas pressure at the inlet to gas valve Is there the correct burner pressure at the test point ? YES YES YES YES YES NO NO NO NO NO Check pilot injector is not blocked Check main injector is not blocked Warning It is important that both the air and flue ducts are cut to their correct lengths also ensure that the flue duct is fully engaged. Failure to comply with the recommended fitting instructions will adversly affect the operation of the appliance. Check pilot flame size YES YES YES YES Check pilot hood position and pilot air flow Check continuity across mains solenoid (5 K OHM) Change gas valve NO Change PCB YES Testing Potentiometer Three Pin Connector Set multimeter to the 2 M OHM scale. Turn potentiometer to the OFF position, connect the multimeter leads to the blue/red wire and centre black/yellow wire of three pin connector. The reading on the multimeter should indicate approx 1 M OHM, switch potentiometer to the ON position, the reading on the multimeter should be approx 1 M OHM. Slowly turn potentiometer knob to the FULL ON position, the reading on the multimeter should decrease, proportionally down to 0 OHMs. Connect multimeter to centre black/yellow wire and red/yellow wire, turn potentiometer knob to fully OFF position, reading on multimeter should be 0 OHM. Switch potentiometer to ON position, slowly turn potentiometer knob to the fully ON position, the reading on multimeter should increase proportionally to 1 M OHM, turn potentiometer off. Reading on multimeter should indicate 0 OHM. Two Pin Connector Check potentiometer is in OFF position. Set multimeter to continuity, connect multimeter leads to both potentiometer leads. Turn potentiometer to the on position, the multimeter's audible alarm should now be sounding to indicate continuity. Replace PCB Replace sensor Check Potentiometer (see table)
Страница 43 PDF
Страница 44
12.0 Short Parts List 44 59 54 90 100 34 33 35 77 83 64 84 98 94 69 42 53 91 12.1 Short Parts List 35 Key Description Model G.C. Manuf'rs No No Part No 53 Burner 30-40-50 364 878 231708 60-70-80 364 879 231709 59 Burner Injector 30 364 880 231354 40 364 881 231355 50 364 882 228104 60 364 873 231776 70 E01 623 239619 80 364 981 231777 54 Pilot Kit All models 170 558 236142 100 Electrode Lead All models 364 745 225826 90 Control Knob All models 364 886 230981 42 Viewing Window Kit All models 364 588 224183 34 Insulation R.H. All models 364 889 230653 33 Insulation L.H. All models 364 890 230652 35 Retaining Clips All models 364 891 230817 77 Gas Valve All models E24 690 245122 98 Overheat Thermostat All models E03 921 241792 84 Fuse All models 364 892 231402 64 Fan 30-40-50 E26 180 246051 60-70-80 E26 213 246052 94 Thermostat All models 379 030 246064 83 PCB All models 379 031 231711 91 Potentiometer All models 379 960 231252 69 Pressure Switch 30, 40, 50 E26 186 246053 60, 70 E26 219 246054 80 E26 221 246055
Страница 44 PDF
Страница 45
13.0 Notes 45
Страница 45 PDF
Страница 46
13.0 Notes 46
Страница 46 PDF
Страница 47
Baxi UK Limited manufacture a comprehensive range of products for the domestic heating market Gas Central Heating Boilers (Wall, Floor and Fireside models). Independent Gas Fires. Renewal Firefronts. Gas Wall Heaters. Solid Fuel Fires. If you require information on any of these products, please write to the Sales Department. 47
Страница 47 PDF
Страница 48
Baxi UK Limited Brownedge Road Bamber Bridge Preston Lancashire PR5 6SN www.baxi.com After Sales Service 08706 096 096 Technical Enquiries 08706 049 049 Comp No 244096 - Iss 5 - 4/01
Страница 48 PDF